Diesel Generator Won't Start? Professional Troubleshooting Guide

ABSTRACT

Learn how to fix a diesel generator that won't start. Step-by-step troubleshooting for fuel system bleeding, battery checks & professional maintenance tips.

Diesel Generator Won't Start? Professional Troubleshooting Guide

When your diesel generator fails to start, follow this systematic troubleshooting approach developed through years of field experience. This guide will help you identify and resolve common starting issues with your diesel generator.


Step 1: Check Starting Power System

  • Use a digital multimeter to measure each battery, ensuring series voltage stabilizes at 24V±0.5V

  • If voltage drops below 23V or shows >0.3V difference between batteries, charge or replace them


Step 2: Inspect Fuel Supply System

  1. Check manual transfer pump for smooth operation and proper resistance

  2. Examine fuel lines for kinks or compression damage

  3. For long-idle equipment, verify diesel fuel hasn't developed contaminants or microbial growth


Step 3: Diagnose High-Pressure Fuel Circuit

  • Loosen the high-pressure fuel pump outlet bolt and crank the engine briefly (≤5 seconds each attempt)

  • Normal condition: Pulsating diesel spray should be visible

  • No fuel output: Indicates air intrusion in fuel lines or transfer pump failure


Step 4: Standardized Fuel System Bleeding Procedure

  1. Primary Bleeding:

    • Open transfer pump outlet connection

    • Operate manual pump until bubble-free fuel flows

    • Retighten connection (28-32N·m torque)

  2. Secondary Bleeding:

    • Loosen fuel filter vent screw

    • Continue pumping until filter housing fills completely

    • Tighten vent screw (15-18N·m torque)

  3. Final Bleeding:

    • Repeat bleeding at high-pressure pump return line

    • Use transparent tubing to monitor air bubble elimination


Professional Recommendations

  • After bleeding, perform 3 consecutive starting attempts (30-second intervals) to remove residual air

  • If the diesel generator still won't start, inspect:

    • Starter motor speed (should exceed 200 rpm)

    • Fuel injector solenoid valve operation

    • Engine compression ratio (cylinder pressure >18 bar)


This guide applies to most domestic and imported diesel generator models. For complex electrical system faults, professional diagnostic tools are recommended for error code reading. Regular maintenance remains the most effective prevention against starting failures.

Field Engineer's Tip: Document key parameters (starting voltage, oil pressure buildup time) after each maintenance for future troubleshooting reference.