Water in Diesel Generator Fuel: Causes & Solutions-EMEAN POWER

ABSTRACT

Learn why water gets into diesel generator fuel, its damaging effects, and expert solutions. Prevent costly damage with EMEAN POWER's proven methods.

When your diesel generator set has difficulty starting or is running abnormally, water in the fuel may be the culprit. Water entering the fuel system will trigger a chain reaction and seriously affect the performance of the unit. The following is a professional analysis solution:

I. Three major sources of water infiltration into the fuel

 

1. Fuel quality problems

 

-The purchased diesel itself contains excessive water (common in non-formal channel fuel)

-Poor container sealing during storage causes water vapor condensation

 

2. Improper storage of diesel generator tanks (the most easily overlooked reason)

 

-When the tank is half full for a long time, the moisture in the air humidity will condense on the tank wall

-Experimental data shows that: 200L tanks can condense 50ml of water per month in a 70% humidity environment

-This problem is more likely to occur when diesel generator sets are parked for a long time

 

3. Physical leakage

 

-Aging of the tank welding seam/seal ring leads to external moisture infiltration

-Failure of the fuel filler cap seal (common in mobile diesel generator sets used outdoors)

 

II. Five major hazards of water in the fuel

 

1. Damage to the starting system

-Water causes poor atomization of the injector nozzle, making it difficult to start the diesel generator set

-Water reacts with sulfur to produce acidic substances, corroding the high-pressure oil pump

 

2. Fuel system corrosion

-Water accelerates the rust of precision parts (actual measurement: 0.1% water content can shorten the life of the pump body by 40%)

 

3. Microbial growth

-The water-oil interface will breed "diesel bacteria", block the filter and produce corrosive metabolites

 

4. Abnormal wear

-Water destroys the lubricating oil film, causing abnormal wear of the plunger pair

 

5. Emergency function failure

-For standby diesel generator sets, water in the fuel may cause failure to start in an emergency

 

III. Professional-level solutions

1. Emergency treatment measures

-Immediately drain the contaminated fuel (note: professional recycling is required)

-Replace the diesel filter (it is recommended to replace the oil-water separator at the same time)

 

2. Preventive maintenance plan

-Check the drain valve at the bottom of the fuel tank every month (it is recommended to use a transparent water collection cup for observation)

-Keep the fuel tank full of oil to reduce the air contact surface

-Add professional fuel desiccant (add 500ml for every 1000L fuel)

 

3. Deep system maintenance

-Use ultrasonic cleaning of fuel lines every year

-Replace all O-rings (fluorine rubber is recommended)

 

EMEAN POWER engineers specially remind: For diesel generator sets that have been parked for a long time, it is recommended to start and run for 30 minutes every 3 months, and drain the water that may condense through the fuel circulation system. Save this guide to ensure that your generator set always gets the best protection.